Back to Chapter 8

 

Pipe Sizing Between First Stage and Second Stage Regulators

(a) Outside Diameter Copper Tubing, Type K

(b) Outside Diameter Refrigeration Tubing

Tubing

Length

Ft.

3/8 In.

0.305

½ In.

0.402

5/8 In

0.527

¾ In.

0.652

7/8 In.

0.745

Tubing

Length

Ft.

3/8 In.

0.311

½ In.

0.436

5/8 In.

0.555

¾ In.

0.680

7/8 In.

0.785

30

284

587

1193

2085

2959

30

299

726

1367

2329

3394

40

243

502

1021

1785

2532

40

256

621

1170

1993

2904

50

216

445

905

1582

2244

50

227

551

1037

1766

2574

60

195

403

820

1433

2033

60

206

499

939

1600

2332

70

180

371

754

1319

1871

70

189

459

864

1472

2146

80

167

345

702

3227

1740

80

176

427

804

1370

1995

90

157

374

659

1151

1633

90

165

401

754

1285

1873

100

148

306

622

1087

1542

100

156

378

713

1214

1769

150

119

246

500

873

1239

150

125

304

572

975

1421

200

102

210

428

747

1060

200

107

260

490

834

1216

250

90

186

379

662

940

250

95

230

434

739

1078

300

82

169

343

600

851

300

86

209

393

670

976

350

75

155

316

552

783

350

79

192

362

616

898

400

70

144

294

514

729

400

74

179

337

573

836

450

66

136

276

482

654

450

69

168

316

538

784

500

62

128

260

455

646

500

65

158

298

508

741

600

52

107

217

379

538

700

54

132

249

424

617

700

52

107

217

379

538

700

54

132

249

424

617

800

48

99

202

353

501

800

51

123

321

394

574

900

45

93

189

331

470

900

48

115

217

370

539

1000

43

88

179

313

444

1000

45

109

205

349

509

1500

34

71

144

251

356

1500

36

87

165

281

409

2000

29

60

123

215

305

2000

31

75

141

240

350

Notes:
  1. Maximum undiluted propane capacities listed are based on a gauge pressure of 10 psi first stage setting and 1 psi pressure drop. Capacities in 1000 Btu/hr.
  2. To convert to capacities at a gauge pressure of 5 psi setting with 10 percent (0.5 psi) pressure drop, multiply values by 0.606. To convert to capacities at a gauge pressure of 15 psi setting with 10 percent (1.5 psi) pressure drop, multiply values by 1.380. Reference NFPA Pamphlet 58, table 11-4.

upbutton.jpg (935 bytes)

 

 

Copper Tube Sizing Between Second Stage Regulator and Appliance

(a) Outside Diameter Copper Tubing, Type K

(b) Outside Diameter Refrigeration Tubing

Tubing

Length

Ft.

3/8 In.

0.305

½ In.

0.402

5/8 In

0.527

¾ In.

0.652

7/8 In.

0.745

Tubing

Length

Ft.

3/8 In.

0.311

½ In.

0.436

5/8 In.

0.555

¾ In.

0.680

7/8In.

.785

10

45

93

188

329

467

10

47

115

216

368

536

20

31

64

129

226

321

20

32

79

148

253

368

30

25

51

104

182

258

30

26

63

119

203

296

40

21

44

89

156

221

40

22

54

102

174

253

50

19

39

79

138

196

50

20

48

90

154

224

60

17

35

71

125

177

60

18

43

82

139

203

80

15

30

61

107

152

80

15

37

70

119

174

100

13

27

54

95

134

100

14

33

62

106

154

125

11

24

48

84

119

125

12

29

55

94

137

150

10

21

44

76

108

150

11

26

50

85

124

200

9

18

37

65

92

200

9

23

43

73

106

250

8

16

33

58

82

250

8

20

38

64

94

300

7

15

30

52

74

300

8

18

34

58

85

350

7

14

28

48

68

350

7

17

32

54

78

400

6

13

26

45

63

400

6

16

29

50

73

Note: Maximum undiluted propane capacities listed are based on a 11" water column setting and 0.5 in water column pressure drop. Capacities in 1000 Btu/hr. Reference NFPA Pamphlet 58, table 11-5.

upbutton.jpg (935 bytes)

 

 

Copper Tube Sizing Between First Stage (High Pressure Regulator) and Second Stage (Low Pressure Regulator)

(a) Outside Diameter Copper Tubing, Type K

(b) Outside Diameter Refrigeration Tubing

Tubing

Length

Ft.

3/8 In.

0.315

½ In.

0.430

5/8 In

0.545

¾ In.

0.666

7/8 In.

0.785

Tubing

Length

Ft.

3/8 In.

0.315

½ In.

0.430

5/8 In.

0.545

¾ In.

0.666

7/8 In.

0.785

30

309

700

1303

2205

3394

350

82

185

345

584

898

40

265

599

1115

1887

2904

400

76

172

321

543

836

50

235

531

988

1672

2574

450

71

162

301

509

784

60

213

481

896

1515

2332

500

68

153

284

481

741

70

196

443

824

1394

2146

600

61

138

258

436

671

80

182

412

767

1297

1996

700

56

127

237

401

617

90

171

386

719

1217

1873

800

52

118

221

373

574

100

161

365

679

1149

1769

900

49

111

207

350

539

150

130

293

546

923

1421

1000

46

105

195

331

509

200

111

251

467

790

1216

1500

37

84

157

266

409

250

90

222

414

700

1078

2000

32

72

134

227

350

300

89

201

375

634

976

           
Note: Maximum undiluted propane capacities listed are based on 10 psi first stage setting and 1 psi pressure drop. Capacities in 1000 Btu/hr. Reference NFPA Pamphlet 58, table 11-6.

Back to Top

Revised January, 1999

 
© 1998-2008 GROWMARK, Inc. All rights reserved.