Pipe and
Tubing Sizing for Liquid Propane |
Liquid Propane
Flow GPH |
Copper
Tubing, Type K.O.D. |
Iron Pipe
(Feet) |
| 3/8" |
½" |
5/8" |
¼" |
3/8" |
1/2" |
¾" |
1" |
1-1/4" |
1-1/2" |
2" |
| |
|
|
Schedule |
Schedule |
Schedule |
Schedule |
Schedule |
Schedule |
Schedule |
Schedule |
| |
|
|
40 |
80 |
40 |
80 |
40 |
80 |
40 |
80 |
40 |
80 |
40 |
80 |
40 |
80 |
40 |
80 |
6 |
910 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
510 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
10 |
328 |
1316 |
|
729 |
416 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15 |
145 |
585 |
|
324 |
185 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
20 |
82 |
329 |
1410 |
182 |
104 |
825 |
521 |
|
|
|
|
|
|
|
|
|
|
|
|
40 |
20 |
82 |
354 |
46 |
26 |
205 |
129 |
745 |
504 |
|
|
|
|
|
|
|
|
|
|
60 |
9 |
36 |
157 |
20 |
11 |
92 |
58 |
331 |
224 |
|
|
|
|
|
|
|
|
|
|
80 |
|
20 |
88 |
11 |
6 |
51 |
32 |
187 |
127 |
735 |
537 |
|
|
|
|
|
|
|
|
100 |
|
13 |
56 |
7 |
4 |
33 |
21 |
119 |
81 |
470 |
343 |
|
|
|
|
|
|
|
|
120 |
|
9 |
39 |
|
|
23 |
15 |
83 |
56 |
326 |
238 |
|
|
|
|
|
|
|
|
140 |
|
|
9 |
|
|
15 |
9 |
61 |
41 |
240 |
175 |
813 |
618 |
|
|
|
|
|
|
160 |
|
|
|
|
|
13 |
8 |
47 |
32 |
184 |
134 |
623 |
473 |
|
|
|
|
|
|
180 |
|
|
|
|
|
|
|
37 |
25 |
145 |
196 |
491 |
373 |
|
|
|
|
|
|
200 |
|
|
|
|
|
|
|
30 |
20 |
118 |
86 |
399 |
303 |
|
|
|
|
|
|
240 |
|
|
|
|
|
|
|
21 |
14 |
81 |
59 |
277 |
211 |
|
|
|
|
|
|
280 |
|
|
|
|
|
|
|
15 |
10 |
60 |
44 |
204 |
155 |
|
|
|
|
|
|
300 |
|
|
|
|
|
|
|
13 |
9 |
52 |
38 |
177 |
135 |
785 |
623 |
|
|
|
|
350 |
|
|
|
|
|
|
|
|
|
38 |
28 |
130 |
99 |
578 |
459 |
|
|
|
|
400 |
|
|
|
|
|
|
|
|
|
30 |
22 |
99 |
75 |
433 |
344 |
960 |
794 |
|
|
500 |
|
|
|
|
|
|
|
|
|
19 |
14 |
64 |
49 |
283 |
225 |
627 |
508 |
|
|
600 |
|
|
|
|
|
|
|
|
|
|
|
44 |
33 |
197 |
156 |
435 |
352 |
|
|
700 |
|
|
|
|
|
|
|
|
|
|
|
32 |
24 |
144 |
114 |
320 |
259 |
|
|
800 |
|
|
|
|
|
|
|
|
|
|
|
25 |
19 |
110 |
87 |
245 |
198 |
965 |
795 |
900 |
|
|
|
|
|
|
|
|
|
|
|
19 |
14 |
87 |
69 |
194 |
157 |
764 |
630 |
1000 |
|
|
|
|
|
|
|
|
|
|
|
16 |
12 |
71 |
56 |
157 |
127 |
618 |
509 |
To Use Chart:
- Having determined the required flow at point of use, locate this flow in
the left hand column. If this falls between two figures, use the larger of the two.
- Determine total length of piping required from source to point of use.
- Read across chart from left (required flow) to right to find the total
length which is equal to or exceeds the distance from source to use.
- From this point read up to find the correct size of pipe required.
Reference Rego LP-Gas Servicemans Manual.
|