Pipe and Tubing Sizing for Liquid Propane

Liquid Propane Flow GPH

Copper Tubing, Type K.O.D.

Iron Pipe (Feet)

3/8"

½"

5/8"

¼"

3/8"

1/2"

¾"

1"

1-1/4"

1-1/2"

2"

     

Schedule

Schedule

Schedule

Schedule

Schedule

Schedule

Schedule

Schedule

     

40

80

40

80

40

80

40

80

40

80

40

80

40

80

40

80

6

910

                                   

8

510

                                   

10

328

1316

 

729

416

                           

15

145

585

324

185

20

82

329

1410

182

104

825

521

                       

40

20

82

354

46

26

205

129

745

504

                   

60

9

36

157

20

11

92

58

331

224

                   

80

 

20

88

11

6

51

32

187

127

735

537

               

100

 

13

56

7

4

33

21

119

81

470

343

               

120

 

9

39

   

23

15

83

56

326

238

               

140

   

9

   

15

9

61

41

240

175

813

618

           

160

         

13

8

47

32

184

134

623

473

           

180

             

37

25

145

196

491

373

           

200

             

30

20

118

86

399

303

           

240

             

21

14

81

59

277

211

           

280

             

15

10

60

44

204

155

           

300

             

13

9

52

38

177

135

785

623

       

350

                 

38

28

130

99

578

459

       

400

                 

30

22

99

75

433

344

960

794

   

500

                 

19

14

64

49

283

225

627

508

   

600

                     

44

33

197

156

435

352

   

700

                     

32

24

144

114

320

259

   

800

                     

25

19

110

87

245

198

965

795

900

                     

19

14

87

69

194

157

764

630

1000

                     

16

12

71

56

157

127

618

509

To Use Chart:
  1. Having determined the required flow at point of use, locate this flow in the left hand column. If this falls between two figures, use the larger of the two.
  2. Determine total length of piping required from source to point of use.
  3. Read across chart from left (required flow) to right to find the total length which is equal to or exceeds the distance from source to use.
  4. From this point read up to find the correct size of pipe required. Reference Rego LP-Gas Serviceman’s Manual.

Back to Top