Back to Propane Home
Chapter 11
Handling Propane
This Chapter contains information on:
Grounding
of Propane Bulk Plants and Bobtails
State Laws have outlined in NFPA Pamphlet 77 requires the grounding of
all Propane bulk storage and bobtails during loading. This Pamphlet is also refereed to in
NFPA Pamphlet 58.
Some bulk plants and bobtails may not be equipped with the grounding
cables and grounding lugs. If present they may not be used regularly. Bulk storage should
be grounded at once and bobtails should be equipped with ground lugs. The bobtail loading
station should be equipped with cable and clamp secured to piping so bobtail can be
grounded at the time of loading.
The cable for bobtail and bulk storage as well as grounding rod can be
secured from local electricians. Grounding lugs and clamps can be secured from GROWMARK
Facility Equipment.
GROWMARK transports are equipped with unloading hoses, with ground wire
included in the hose. Therefore, when the hose is connected, the transport is grounded to
the bulk plant.

Bobtail Loading
- Block wheels using wheel chocks each time unit is parked, being loaded or
off-loading.
- Hook up liquid and vapor hose to Bobtail.
- Start at bulk plant tank by opening all valves and continue opening each
valve as you come to them.
- Turn on pump after opening liquid valve at Bobtail.
- Open vapor valve at Bobtail after pump has been turned on.
- Using this sequence, there is less chance of the excess flow valve
slugging off.
- If excess flow valve does slug off, it may take two to three hours to
equalize and open, so be patient.
- Load Bobtail to 85% maximum only.

Hose Management Program
- Pressure test required for new/repaired/modified delivery hose
- Visual inspection of delivery hose assembly after each unloading
- Hoses will be marked for service intervals
- Monthly hose inspections required on delivery units
- Annual delivery hose assembly inspections by a Registered Inspector
- All hose inspections records are to be recorded and filed

Guide to Hose Inspection
Propane hose should be given a brief examination every time it is used.
When the outer covering is rubbed off to the extent that the fabric-reinforcing web begins
to show the hose should be removed from service. Hose should be removed from service
immediately whenever blistering or loose outer cover is observed. Complete examination
according to the following procedure should be made at least once every other month and
preferably oftener.
Check the DOT regulations in your state for daily hose inspection,
pressure testing, and replacement. The following are suggested practices for hose
inspection.
- The hose should be laid out as straight as possible to avoid chinking
during the examination. The hose should be examined closely for cuts, abrasion, soft
spots, bulges, and similar defects.
- Cuts in the hose covering which have damaged or exposed the reinforcement
fabric would be sufficient cause to remove the hose from service. If properly trained and
equipment available, good portions of the hose may be returned to service.
- Small cuts and nicks in the outer cover should generally not be cause for
hose replacement unless the rubber involved is loose or the reinforcement is exposed.
Note: Pricking the cover in the manufacture of this type of hose is common and good
practice. Obviously, uniform pricking in the cover should not be considered as cuts or
nicks in the covering.
- The area adjacent to the fitting for 18 in. back from the fitting should
be carefully examined by pressing he hose with the thumb to detect any soft spots or
bulges. Hoses having such weak sections should be removed from service immediately. This
hose may be returned to service provided the damaged areas(s) have been properly repaired
and pressure tested.National Propane Gas Associations Technology & Standards
Committee prepared this hose examination procedure as one of its guides for upgrading
Propane industry operations.
- Hose should be removed from serviced immediately and inspected whenever
blistering or loose outer cover is observed.
- Each coupling should be inspected for slippage, which will be evident by
misalignment of the coupling of the hose end and /or scored or exposed area where slippage
has occurred. Any evidence of slippage shall require dressing a new end on that section of
the hose and re-installation of the coupling. If the condition of the hose is such that
this is not practical, then the hose shall be removed from service and replaced.
- Localized defects may be cut out and the good portions of the hose put
back in service where possible.
- Hose subjected to unusual abuse such as chinking or flattening by being
ran-over by the vehicle shall be removed from serviced immediately and inspected by the
above procedure.
- If the hose was depressurized and passes all the above preliminary
inspections, the hose shall then be subjected to product pressure for its service
inspection again for defects. Hose or sections of hose, passing this inspection may be
returned to service. Note: While this guide does not include a procedure for hydrostatic
pressure test, it should be noted that some members of industry have found such a test to
be of great benefit. When an operator elects to use such a test the test pressure should
not exceed 1 ½ times the maximum pressure to which the hose is subjected. Such testing
may be done in addition to this recommended visual inspection procedure.
- As a reminder this Visual Inspection includes regularly checking for
cuts, blisters, exposed fabric, soft spots and damaged fittings.

Federal
Department of Transportation
Effective July 1, 1999
Emergency Discharge System Inspection/Maintenance Program
- Monthly visual inspection of discharge system and components are required
- Monthly check of internal valve (meter creep test is acceptable) and
testing of all emergency devices
- Annual inspection of discharge system by a Registered Inspector required
- All discharge system inspections will be recorded and filed
Emergency Operation Procedures
Written operating procedure are required for all transfer operations
with copy in or on cargo tank motor vehicle. Describe Emergency Discharge Control System
(EDCS) features and indicate if off-truck and/or passive system is part of EDCS.
Unloading Procedures
Before each transfer, operator must verify that each component of the
discharge system is of sound quality, is free of leaks, and that connections are secure.
This determination must be made after the pressure in the discharge system has reached no
less than equilibrium with the pressure in the cargo tank.
Person attend unloading must remain within 45.72 meter (150 ft.) of the
cargo tank and 7.62 meter (25 ft.) of the delivery hose throughout the unloading operation
and must observe both the cargo tank and the receiving tank at least once every five
minutes during unloading operations that take more than five minutes to complete.
If there is an unintentional release during unloading, the internal
self-closing stop valve must be activated promptly. The person unloading the cargo tank
motor vehicle must promptly shut down all motive and auxiliary power equipment.
For vehicles equipped with off-truck remote shut-off mechanisms, the
activation device must be tested and proven operational from a distance of 150 feet before
the first delivery of each day.
New Hardware
Fusible elements on cargo tanks not currently so equipped
Off-truck remote enable the operator to stop the delivery of
lading from any location he may need to be during unloading. Mechanism must close internal
valve and shut-off engine. Internal valve must remain closed until manually reset.
For cargo tanks over 3,500 gallons making obstructed view deliveries
emergency discharge control system that will automatically shut-off the flow
without the need for human intervention within 20 seconds of an unintentional release
caused by complete separation of the discharge hose OR off-truck remote with 5-minute
query feature.
All new and rebuild trucks will be equipped with off-truck remotes
systems
All new manufactured and rebuilds of tanks of over 3,500 gallon will
have a passive shut-down
All new and rebuilds will be equipped with fusible elements

Pump Out of Bottom Fill Tanks
- Using Rego 3119A liquid withdrawal valve connect to double check filler
valve.
- Connect pump-out hose to 3119A valve and pump inlet connection.
- Connect bobtail delivery hose to Bobtail tank connection.
- Install ticket in meter register.
- Open delivery hose valve and Bobtail tank valve to direct Propane in
domestic tank through Bobtail pump into Bobtail tank.
- Rotate level on 3119A valve to open filler valve.
- Engage Bobtail pump.
- Propane should be moving from the domestic tank into the Bobtail tank, if
not re-check valves to and from Bobtail pump.

Pump
Out of Spray Fill Tanks Through Rego Check-Loc or Fisher Safe-E Valves
- Remove plug marked "Check-Loc" or "Safe-E Valve" on
the face of plug. After loosening approximately two threads, a hole in the cap should have
released gas pressure except a little seepage.
- Remove plug and install Rego 7550UV liquid withdrawal Valve.
- Connect pump-out hose to 7550UV valve and Bobtail pump inlet.
- Connect Bobtail delivery hose to Bobtail tank connection.
- Install ticket in meter register.
- Open delivery hose valve and Bobtail tank valve to direct Propane in
domestic tank through Bobtail pump into Bobtail tank.
- Open 7550UV valve.
- Check Check-Loc or Safe-E Valve for rate of flow and pump at one to two
gallons less, to keep excess-flow valve from closing.
- Activate Bobtail pump
- You should now be pumping liquid from the domestic tank to the Bobtail
Tank.

Installing Alcohol in Bulk
Tanks
When moisture is suspected in a Propane system, alcohol can be used to
neutralize the Propane. Alcohol can be injected into tanks while under pressure. A rule of
thumb to follow is to inject:
| 500 gallon tank |
5 pints |
| 1000 gallon tank |
10 pints |
| (1 ¼ gallon Anhydrous Methanol Alcohol per
1000 gallon Propane) |
- Using alcohol injector, fill chamber with Methanol Alcohol or Anhydrous
Methanol Alcohol
- Connect 3119A withdrawal valve to the double check filler valve.
- Connect 1 ¾" Acme, bottom connection of alcohol injector, to 3119A
valve.
- Connect vapor hose connection to vapor equalization valve on tank.
- Open alcohol injector valve.
- Open 3119A valve by rotating side lever on 3119A valve.
- Pressure will equalize and the alcohol will run into storage tank.
- An angle adapter should be used on end mount storage tanks, allowing
alcohol to flow into tank.
Note: You may inject Methanol Alcohol into your
bulk plant storage tank by following the suggested procedures.
- Schedule a daytime delivery and request the driver to stop at Office for
your assistance.
- Have Methanol Alcohol available and ready to be placed in the transport
unloading hose.
- Assist transport driver in pushing Alcohol into tank as Propane is
unloading.

Territory Delivery Management
It is human nature to resist change so maybe you would like the Fuel
Tracker system if we told you here and now that we dont want to take your route
system away from you. We want you to retain that geographic spotting and location of your
patron, but only deliver when they are in need of Propane.
There are advantages for the salesman wanting to see his patrons. Energy
Specialists are selling them gasoline, diesel fuel, motor oil, grease, paint, TBA, burner
fuel, Propane, etc. The more often the salesperson has the opportunity to talk to farm
patrons, the better off both of them are. The only difference between a route system and
Fuel Tracker is the fact that the drops per stop are a third larger- meaning a savings of
trucking and bookkeeping costs.
Isnt this how your route system works? You go from home to home
stopping at each customer, filling each tank and repeating this on a regular basis. You
seldom or never let your customers run out of fuel. But to do this, the patron who
burns the most fuel is the man who establishes the frequency with which you service hour
route or is it the patron with the smallest storage? You rationalize this by saying,
"I was going by anyway, so why not fill everybody since I am in the
neighborhood?" So you see the big difference is this: you retain the geographical
spotting of your patrons, but only deliver when they need fuel and can take a minimum
fill. This is where you are going to save money.
A few questions have been surfaced:
- "We have too many people who dont pay promptly, their credit
is shaky." With the Fuel Tracker system, you know when those people are coming up for
a delivery and you can work on them to make payments several days or a week in advance,
depending on how far ahead of the degree day you are scanning your file. Your prediction
of when they will run out of fuel, can be verified by the patron looking at his own tank.
You then have an alternative. Pay or else no delivery.
- The customer says that he will call you. You still cannot deliver to him
until he gives you permission. Call him on the phone when he is due for a delivery and
soon he will see that you know more about this use of fuel than he does and he will be
ready to accept automatic Fuel Tracker deliveries. Remember also that the patron who says
he will call you usually is reminded to call when he sees your truck going by his home and
that means a special trip which costs you money.
- The patron says they only want 100 gallon at a time. If they are worth
being a customer, (Im not even calling them a patron) put them on the Fuel Tracker
system. Then at least you can get them when you are in the neighborhood and you know when
they need that 100-gallon.
Fuel Use Tracking Systems
Fuel Tracker is an automated Heating Oil and LP Gas Scheduling/Routing
System, eliminating the need for customers to call for service. It anticipates each
customers use of heating oil/LP based on past history and degree-days. Customers can
go on vacation without worrying about running out of fuel.
The salesmen will be more efficient because deliveries will be scheduled
for them they wont always be operating on an emergency basis or going out of
their way to check on customers whose tanks are still 80% full.
Sales tickets automatically interface from TICKET MAKER to Fuel Tracker
to record the fill. The calculation process then starts over as each days degree-day
is recorded.
Also now available in Fuel Tracker is the ability to automatically
account for fuel used for hot water tanks, gas clothing dryers, and gas stoves in the
summer when there are no degree days to record.
Degree Day Systems- defining a Degree-Day system is simple. It is
easy to set up and maintain. The one important factor is called, "K-Factor" or
"Burning Rate." In other words, you must find out how many degree days is will
take to burn one gallon of fuel, or divide the gallons used into the number of degree
days, since last filling. K-Factors are expressed and vary between 1 to 5, with averages
about 1.5 to 3.5.
- Equipment and forms required:
- Hidy Brown, Johnson or method of recording Degree Days
- Degree Day Cards for each patron
- Degree Day indexes for storing
- Degree Day File
- Degree Day count for previous beating season
- How to get started:
Patrons who used Propane last heating season
- Go to your delivery records and pick out two different consecutive
deliveries (1) consecutive deliveries in October or November (2) consecutive deliveries in
January or February.
- Picks out dates of two deliveries assuming that both deliveries were
fills. Go to the Degree Day chart and find number of Degree Days accumulated between these
two dates. Compute the K-Factor (the number of Degree Days taken to burn one gallon of
fuel. Divide the gallons used into the number of Degree Days.)
- After doing this exercise twice for the two different periods, arrive at
an average K-Factor and insert this factor in the patrons Degree Day card.
- Make sure to fill storage this summer and enter Degree Day figure in the
patrons Degree Day figure for the next delivery based upon the amount of storage.
Always allow a 10-15% of tank size for emergency purposes and mis-calculations.
- Multiply the K-Factor by gallons to deliver and this will give you the
Degree Days for the next delivery. Enter this figure on the card and put in the proper
index.
- After the first delivery is made in the fall of the year, refigure the
K-Factor because of variance between Max-Min method and recording method. Erase the old
K-Factor with newly arrived figure.
- Your work is now done. You should periodically recheck K-Factor if actual
delivery of fuel varied from what your Degree Day card shows. Mr. Patron could add to his
BTU load and use fuel faster than the K-Factor reflects.
New Patrons:
- You must make two deliveries, keeping record of both gallons delivered
and Degree Days for both deliveries. Deliveries must be fills. At this time, a K-Factor
can be determined for the new patron.
- Proceed as for old patrons.
Summary:
- Degree Day system improves service.
- Lowers operating costs.
- Saves time.
- Helps control credit.
- Gets Summer Fill.
- Keeps tanks full.
- Can be used as an "Merchandising Tool."
- Delivery control is manageable.
- Illness, emergencies, or other circumstances will not slow fuel
deliveries.
Visit the Member Company Computer Services webpage for more information
on Fuel Tracker.
Back to Top |